Product Dose

USES:

Deep cleaning of outdoor condenser coils to restore efficiency and increase performance of the system.

DILUTION RATIOS:

Because RXSOL-16-2697-003 is highly concentrated, it must be diluted prior to use. Dilution also improves penetration into the coil and increases product performance. Actual dilution ratios will vary according to the application. The following is intended as a general
guideline:

  • Up to 8-10 parts water to 1 part RXSOL Active SK COIL Cleaner yellow  for light cleaning and brightening, when expanding foam is not required.
  • 3-5 parts water to 1 part RXSOL Active SK COIL Cleaner yellow  for foaming action on difficult cleaning tasks.
  • 1-2 parts water to 1 part RXSOL Active SK COIL Cleaner yellow  for use as a high foaming,aluminum finned, air cooled condenser coil cleaner.Use the minimum concentration required to accomplish your task.

Note: Do not use RXSOL-16-2697-003 at concentrations greater than 1:1 (less than 1 part water to 1 part RXSOL-16-2697-003 . Rinse the treated surfaces as well as the surrounding area thoroughly after use.

APPLICATION METHODS:

Low pressure, acid resistant tank sprayers are recommended.
Regardless of application method, avoid inhalation of mist or contact of liquid or mist with skin.

SUGGESTED INSTRUCTIONS FOR USE:

  •  When handling RXSOL-16-2697-003 or any other strong chemical, be sure to wear chemical imperviousgloves,apron and splash goggles.
     
  • Determine required dilution ratio for the specific application. It is recommended to start with a dilution ratio of 10:1 and increase concentration until the desired results are achieved.
     
  • As with mixing all acids, place the desired amount of water into the tank and then add RXSOL-16-2697-003
     
  •   Turn off fans and allow hot coils to cool before applying.
     
  • Using plain water, wet both the condenser coil as well as the area surrounding the equipment. Wetting the coil with water aids in product penetration and performance.
     
  • Apply the properly diluted product to the coil surface. Whenever possible, apply solution from the outlet side of the coil. Allow product to remain on surface, normally 5-10 minutes. Do not allow product to dry on the coil. Note: In extreme cases, application may have to be repeated to achieve desired results.
  • If foaming does not occur, check for extreme grease buildup which will slow cleaning process. Foaming may not occur if coil is coated or painted.
     
  •   Rinse coils, tools and surrounding area thoroughly after completing the coil cleaning process

RX MARINE INTERNATIONAL is most popular chemicals source in INDIA, Keeping ready stock at 5 LOCATION which includes Mumbai, Kandla - Gandhidham, Vizag - Visakhapatnam, Ennore - Chennai, Kolkata more then 3000 types of chemicals. Please click here to get PRODUCT Categories details http://rxmarine.com/Products

 

Mail Us for any PRODUCT related information and purchase inquiry : mail@rxmarine.com ( This mail is for customer / Buyer only ) And if you wants to add your hand as a supplier, And if you have volume manufacturing capacity of chemicals, pl. drop your mail at rxmarine@gmail.com ( This mail is for supplier only )