During Circulation of water mainly controlling of 2 factors required : -
SCALE CONTROL in closed water cooling systems - Diesel and gas engines releasing high temperature due to that water present in jacket cooling system increases its tendency to deposit scale. To avoid scale formation water softener like Zeolite gradual buildup of scale in cylinders and cylinder heads. Where condensate is available, it is preferred for closed system cooling water makeup. Where condensate is not available, zeolite softening should be applied to the makeup water.
CORROSION CONTROL An increase in water temperature causes an increase in corrosion. At high temperature solubility of oxygen in water decreases due to that Corrosion rates increasing inside the system. This occurs because the lower solubility of oxygen with increasing temperatures in a freely vented system decreases the corrosion rate faster than the rise in temperature increases it. However, in many closed systems, the dissolved oxygen entering the system in the makeup water cannot be freely vented, resulting in the release of oxygen at points of high heat transfer, which may cause severe corrosion. Untreated systems can suffer serious corrosion damage from oxygen pitting, galvanic action, and crevice attack. Closed cooling systems that are shut down periodically are subjected to water temperatures that may vary from ambient to 180°F (82°C) or higher. During shutdown, oxygen can enter the water until its saturation limit is reached. When the system is returned to high-temperature operation, oxygen solubility drops and the released oxygen attacks metal surfaces.
The three most reliable corrosion inhibitors for closed cooling water systems are chromate, molybdate, and nitrite materials. Generally, the chromate or molybdate types have proven to be superior treatments.